29
7 Special Parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
7-00
Motor full load current setting
30~120%
85
7-01
Motor no load current setting
0~90%
30
7-02
Auto-torque compensation
setting
0.0~1.0
0.0
7-03
Auto slip compensation setting
0.0~10.0
0.0
7-04~7-10
(Reserved)
7-11
Motor rated power
500~3000
1450
7-12
Motor pole number
0~30
4
7-13
Motor rated revolution
5.0~400
50.0
7-14~7-33
Reserved
8 High Function Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory setting
8-00
DC braking level setting
0~100%
0
8-01
DC braking time setting at starting
0.0~60.0S
0.0
8-02
DC braking time setting at stopping
0.0~60.0S
0.0
8-03
Starting frequency of DC braking at
stopping
0.1~60.0Hz
1.0
8-04
Restarting after momentary power
loss
0:Stop running after momentary power loss
0
1:Run continuously after momentary power
loss, track upwards from frequency after
power loss
2:Run continuously after momentary power
loss, track downwards from frequency after
power loss
8-05
Max allowable time for power loss
0.3~5.0S
2.0
8-06
Speed tracking time for B.B
0.3~5.0S
0.5
8-07
Max current setting for speed
tracking
30~200%
150
8-08
Max of inhibited frequency setting1
0.0~400Hz
0.0
8-09
Min of inhibited frequency setting1
0.0~400Hz
0.0
8-10
Max of inhibited frequency setting2
0.0~400Hz
0.0
8-11
Min of inhibited frequency setting2
0.0~400Hz
0.0
8-12
Max of inhibited frequency setting3
0.0~400Hz
0.0
8-13
Min of inhibited frequency setting3
0.0~400Hz
0.0
8-14
Fault restarting times
0~10
0
8-15
AVR function options
0:AVR function available
1
1:AVR function unavailable
2:AVR function cancelled during
deceleration
8-16~8-18
Reserved
8-19
Automatic energy saving
1: no processing
0
2: energy saving
8-20
Error restart times automation reset
time
1~100 mins.
10
8-21
Reserved
8-22
Error restart delay time
0.1~20.0s
2.0