24
2) In 2-00 and 2-01, when 2-00 has been set as 6 or 7 (controlled by UP/DOWN), 2-01 can’t be set as 6 or 7 again.
3) The parameter of 2-07 is valid only when the frequency is given by analog input AVI and input set 0. If the frequency is
given by AVI, but press the STOP key, the inverter will stop still according to the mode of 2-04.
3 Output Function Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory setting
3-00
Random frequency agreement setting
1.0~400Hz
1.0
3-01
Count value agreement setting
0~999
0
3-02
Appointed count agreement setting
0~999
0
3-03
Fwd run reference delay setting
0.0~60.0s
0.0
3-04
Rev run reference delay setting
0.0~60.0s
0.0
3-05
Multifunctional output contactor
indication
Normally Open Contactor(RA-RC)
Normally Closed Contactor(RB-RC)
0: No function
8
1: Reference during running
2: Set frequency agreement reference
3: Reference during zero speed
4: Over-torque detection reference
5: Reference during BB
6. Low voltage detection reference
7:Motor drive operation mode
reference
8: Fault reference
9:Random frequency agreement
reference
10:Reference during program
auto-running
11.Reference of step running
completion.
12.Reference of program running
completion.
13: Program running pause
14: Set count agreement
15: Appointed count agreement
16: Driver preparation completion
17: Fwd run direction reference
18: Rev run direction reference
19: Fwd/ Rev run direction reference
3-06
Analog output setting
0:output frequency 1 (before slip
compensation)
0
1:output
frequency
2 (after slip
compensation)
2:Analog current meter(0 to 250% of
rated current)
3: output voltage
4: DC bus voltage
5: consumed power
3-07
Reserved
3-08
Analog output gain selection
1-200%
100