OVERVIEW OF THE PARAMETERS
INSTALLATION
Point name
Status
Default Units
Text displayed*
Description
16
hr_deg
From -16.7
to 16.7
From -30.0
to 30.0
^C
^F
Heating reset Deg. value
Heating reset deg. value
* It depends on the selected language (English by default).
USER CONFIGURATION MENU – USERCONF
Point name
Status
Default Units
Text displayed*
Description
1
use_pass
-
212
-
User Password
Password required for User access
Configuration menu
2
alert_r
no/yes
no
-
Alarm Relay for Alerts?
Alarm relay status. The alarm
output relay is used for "alarm" +
"alert"
* It depends on the selected language (English by default).
MISCELLANEOUS CONFIGURATION MENU – MISC_CFG
Point name
Status
Default
Units
Text displayed*
Description
1
HP HYBRID CONFIG
Heat pump configuration
2
hh_dtmax
From 30 to
600
360
min
DHW Max Cycle Time
DHW maximum cycle time
3
hh_minht
From -25.0
to 5.0
From -13.0
to 41.0
-10.0
14.0
°C
°F
Min. OAT In Mechanical Heating
Minimum OAT with mechanical
heating ON
4
hh_oatph
From -20.0
to 25.0
From -4.0
to 77.0
7.0
44.6
°C
°F
HP Stop in OAT Peak Hour
Heat pump stop in OAT peak hour
5
hh_oatop
From -20.0
to 25.0
From -4.0
to 77.0
2.0
35.6
°C
°F
HP Stop in OAT Not Peak Hour
Heat pump stop in OAT not peak
hour
* It depends on the selected language (English by default).
SCHEDULING MENU – SCHEDULE
Point name
Status
Default
Units
Text displayed*
Description
1
OCCPC01S
-
-
-
OCCPC01S - Scheduling Menu
Unit on/off timer
2
OCCPC02S
-
-
-
OCCPC02S - Scheduling Menu
Unit setpoint selection timer
* It depends on the selected language (English by default).