110
GENERAL INFORMATION
Minimum
Maximum
Water heat exchanger
Entering water temperature (at start-up)
7.5
(1)
30
°C
Leaving water temperature (in operation)
5
(2)
20
°C
Inlet/outlet temperature difference
3
(2)
10
°C
Air-cooled standard exchanger
Inlet air temperature with full load
0
48
°C
Inlet air temperature with partial load
0
48
°C
Air-cooled exchanger. Winter operation or Xtra Fan
(3)
option
Inlet air temperature with full load
-20
46
°C
Inlet air temperature with partial load
-20
48
°C
Hydronic module
(4)
- Inlet air temperature
Without pump
0
-
°C
With Single or Double (LP or HP) pump option
0
-
°C
With Backup Tank option
0
-
°C
Note:
Do not exceed maximum operating temperature.
(1) For entering water temperature at start-up lower than 7.5°C contact the manufacturer.
(2) If leaving water temperature is lower than 5°C the use of the anti-freeze is mandatory.
(3) Channelled machines (Xtra Fan option). This operating range applies for up to 130 Pa static pressure for NXH 072 - NXH 084 and NXH
142 - NXH 164 sizes, and up to 240 Pa for all other sizes.
(4) It defines the anti-freeze protection temperature of the hydronic components for use without glycol. In case of storage and trans-
port of NXH units, the min. and max. temperature limits are -20°C and +48°C. It is recommended to take these temperature values
into account in case of transport in containers.
NXH models - Cooling mode
0
5
10
15
20
25
30
35
40
45
50
0
5
10
15
20
25
Full load
Minimum load
0
5
10
15
20
25
30
35
40
45
50
0
5
10
15
20
25
Ambient air temperature (°C)
Ambient air temperature (°C)
Evaporator leaving water temperature (°C)
Evaporator leaving water temperature (°C)
NXH with silenced plus option
NXH silenced version
Содержание 20120391
Страница 93: ...93 PANORAMICA DEI PARAMETRI INSTALLAZIONE ...
Страница 169: ...169 ALARM CODES INSTALLATION ...
Страница 185: ...185 OVERVIEW OF THE PARAMETERS INSTALLATION ...
Страница 186: ......
Страница 187: ......