171
OVERVIEW OF THE PARAMETERS
INSTALLATION
GENERAL PARAMETER MENU
Point name
Status
Units
Text displayed*
Description
1
CTRL_TYP
From 0 to 2
-
Local=0 Network=1 Remote=2
Operating mode: 0 = Local, 1 =
Network,
2 = Remote
2
STATUS
xxx
-
Operating status
Unit operating status: 0 = Off, 1 =
Running, 2 = Stopped, 3 = Delay, 4
= Lockout, 5 = Ready,
6 = Bypass, 7 = Defrost, 8 = Opera-
tion test, 9
= Test
3
ALM
xxx
-
Alarm Status
Alarm status
4
min_left
From 0 to 0
min
Minutes left to Start-up
Minutes left to unit start-up
5
HEATCOOL
Heat/Cool Status
Heating/Cooling status
6
HC_SEL
From 0 to 2
-
Heat/Cool selection
Heating/Cooling selection
7
0=Cool 1=Heat 2=Auto
0=Cool, 1=Heat, 2=Auto
8
SP_SEL
From 0 to 2
-
Setpoint Selection
Setpoint selection
9
0=Auto. 1=Spt1. 2=Spt2
0 = Auto, 1 = Setpoint 1, 2 = Set-
point 2
10
SP_OCC
no/yes
-
Setpoint Occupied?
Setpoint occupied?
11
CHIL_S_S
enabled/disabled
-
Network: Start/Stop control
Unit start/stop through Network
When the unit is in Network mode,
it is possible to force the start/stop
control
12
CHIL_OCC
no/yes
-
Network: Control Occupied
Time unit programming through
Network: When
The unit is Network mode, it is
possible to use the forced value in-
stead of the real occupation status
13
CAP_T
From 0 to 100
%
Total Capacity Percentage
Unit Total Capacity
14
CAPA_T
From 0 to 100
%
Circuit A Total Capacity
Circuit A total capacity
15
CAPB_T
From 0 to 100
%
Circuit B Total Capacity
Circuit B total capacity
16
DEM_LIM
From 0 to 100
%
Active Demand Limit Value.
Active demand limit value: When
the unit is in Network mode, the
minimum value will be used com-
pared to the external limit switch
contact status and the requested
limit switch setpoint.
17
SP
-
°C / °F
Current Setpoint
Current setpoint
18
CTRL_PNT
From -20.0 to 67.0
From -4.0 to 153.0
°C
°F
Control Point
Control point: Water temperature
that must be produced by the unit
19
EMSTOP
enabled/disabled
-
Emergency Stop
Emergency stop
* It depends on the selected language (English by default).
TEMPERATURE MENU – TEMP
Point name
Status
Units
Text displayed*
Description
1
EWT
-
°C / °F
Entering water Temp
Entering water temperature: Used
to control capacity
2
LWT
-
°C / °F
Leaving water Temp
Leaving water temperature: Used to
control capacity
3
OAT
-
°C / °F
Outside Temperature
Outdoor air temperature: Used to
determine various control mecha-
nisms such as heat/cool switching,
heater operation, defrost cycle
4
CHWSTEMP
-
°C / °F
Master/Slave Common Temp
Master/Slave Common Temperature
5
SCT_A
-
°C / °F
Saturated Condensing Temp A
Saturated condensing temperature,
circuit A
6
SST_A
-
°C / °F
Saturated Suction Temp A
Saturated suction temperature,
circuit A
7
SCT_B
-
°C / °F
Saturated Condensing Temp B
Saturated condensing temperature,
circuit B