179
OVERVIEW OF THE PARAMETERS
INSTALLATION
GENERAL CONFIG MENU – GENCONF
Point name
Status
Default
Units
Text displayed*
Description
1
lead_cir
From 0
to 2
0
-
Leading Cir Sequence
Leading circuit sequence
-
0=Auto 1=A advance 2=B Advance
0 = Automatic switching
1 = Advance Circuit A
2 = Advance Circuit B
2
seq_typ
no/yes
no
-
Staggered Charging Sequence
Staggered charging sequence (unit
with double circuit)
3
ramp_sel
no/yes
no
-
Ramp Charging Selection
Ramp charging sequence
4
off_on_d
From 1 to
15
1
min
Unit Delay from Off to On
Unit Delay from OFF to ON
5
nh_limit
From 0 to
100
100
%
Night Capacity Limit
Night capacity limitation
6
nh_start
00:00
00:00
-
Night Mode Start Time
Night mode start time
7
nh_end
00:00
00:00
-
Night Mode End Time
Night mode end time
* It depends on the selected language (English by default).
PUMP CONFIGURATION MENU – PUMPCONF
Point name
Status
Default
Units
Text displayed*
Description
1
pump_seq
From 0
to 4
0
-
Water Pump Sequence:
0 = No pump
1 = One Pump Only
2 = Two Automatic Pumps
3 = Manual Pump no.1
4 = Manual Pump no.2
Water pump sequence: 0 = No
pump
1 = One pump only (unit with one
pump)
2 = Two pumps with automatic
control
3 = Pump 1 selected (unit with two
pumps)
4 = Pump 2 selected (unit with two
pumps)
2
pump_del
From 24
to 3000
48
hour
Pump Auto Rotation Delay
Pump automatic rotation delay
3
pump_per
no/yes
no
-
Pump Jamming Protection
Pump jamming protection
4
pump_sby
no/yes
no
-
Pump Stop During Standby
Pump is stopped when unit is in
standby
(Heat pumps only)
5
pump_loc
no/yes
yes
-
Flow control with Pump in Off
mode
Water flow is controlled when
pump is off
* It depends on the selected language (English by default).
HEAT/COOL CONFIG MENU – HCCONFIG
Point name
Status
Default
Units
Text displayed*
Description
1
auto_sel
no/yes
no
-
Auto-switching Selection
Heating/Cooling automatic switch-
ing
2
cr_sel
From 0
to 3
0
-
Cooling Reset Selection
Cooling reset
3
hr_sel
From 0
to 3
0
-
Heating Reset Selection:
0=None, 1=OAT,
2=Delta T, 3= 4-20mA Analogue
Heating reset:
0 = no reset
1 = Reset according to OAT
2 = Reset according to delta T
3 = Reset according to 4-20 mA
analogue input
4
heat_th
From
-20.0 to
0.0
From -4.0
to 32.0
-15.0
5.0
°C
°F
OAT Heating Threshold
OAT heating threshold