It is forbidden to lay the power supply and room thermostat cables in the vicinity of any hot surfaces (delivery pipes). If there
is a risk of contact with hot parts, with temperatures exceeding 50°C, a suitable type of cable must be utilized.
2.11.1
Cable sizing
The installer is responsible for cable sizing, which depends on the characteristics and regulations that will apply. The tables below
may help sizing cables correctly.
2.11.2
Unit electric data (without hydronic module)
NXC - NXH
Max. section
that can be
connected
(1)
Calculation of the favourable case
Calculation of the unfavourable case
Section
(2)
Maximum
length of a
voltage drop
< 5%
Cable type
(3)
Section
(2)
Maximum
length of a
voltage drop
< 5%
Cable type
(3)
sq.mm (per
phase)
sq.mm (per
phase)
m
-
sq.mm (per
phase)
m
-
044
1 x 95
1 x 16
165
XLPE copper
1 x 25
300
PVC copper
048
1 x 95
1 x 16
165
XLPE copper
1 x 25
300
PVC copper
056
1 x 95
1 x 16
165
XLPE copper
1 x 25
300
PVC copper
064
1 x 95
1 x 25
210
XLPE copper
1 x 35
305
PVC copper
072
1 x 95
1 x 35
220
XLPE copper
1 x 50
350
PVC copper
080
1 x 95
1 x 35
220
XLPE copper
1 x 70
380
PVC copper
084
1 x 95
1 x 35
220
XLPE copper
1 x 70
380
PVC copper
096
1 x 95
1 x 35
220
XLPE copper
1 x 70
380
PVC copper
104
1 x 95
1 x 70
280
XLPE copper
1 x 95
410
PVC copper
122
1 x 95
1 x 70
280
XLPE copper
1 x 95
410
PVC copper
142
1 x 185
1 x 95
305
XLPE copper
1 x 185
465
PVC copper
164
1 x 185
1 x 120
320
XLPE copper
1 x 185
465
PVC copper
(1) Connection capacity really available for each machine. They are defined according to the size of the connection terminals, the size
of the access opening of the electric box and the space available inside the electric box.
(2) Result of selected simulation considering the hypothesis indicated.
(3) If the maximum section is calculated for an XLPE cable, it means that a selection based on the PVC cable can exceed the connection
capacity really available. You need to pay attention to the selection. The direct contact protection at the electric connection point
is compatible with an additional terminal extension. The installer must determine whether this is required according to the cable
sizing calculation.
Description
NXC - NXH
044
048
056
064
072
080
084
096
104
122
142
164
Power supply circuit
Rated voltage
400 - 3 -50
V-ph-Hz
Voltage range
360 - 440
V
Control Circuit supply
24 V through internal transformer
-
Unit operating rated current
(3)
A&B circuit
25.6
29
33
36
42.4
52.8
53.4
55.4
61.7
77.3
84.8 105.6
A
Max input operating power
(2)
A&B circuit
19.5
22.3
24.5
27.9
31.2
35.8
35.6
42.3
45.6
52.5
62.4
71.6
kW
Unit cos phi
at maximum power
(2)
0.83
0.81
0.81
0.83
0.81
0.78
0.78
0.83
0.81
0.79
0.81
0.78
-
Unit maximum operating current (Un-10%)
(5)
A&B circuit
38
49.2
51.4
58.4
74.8
79.6
80.2
89
110.3
117.5
149.6 159.2
A
Unit maximum current absorption (Un)
(4)
A&B Circuit - Standard unit
34.8
44.8
46.8
52.8
67
73
73.6
80.6
98.6
107.6
134
146
A
Maximum inrush current, standard unit (Un)
(1)
A&B circuit
113.8 134.8 142.8 145.8
176
213
213.6 173.6 207.6 247.6
243
286
A
Maximum inrush current, static starter unit (Un)
(1)
A&B circuit
74.7
86.5
93.8
96.2
114.4 139.8 139.8 130.4 155.4 181.4 186.4 215.4
A
(1) Maximum instantaneous inrush current (maximum operating current of the smallest compressor(s) + fan(s) c locked rotor
current of the biggest compressor).
(2) Input power, to the unit continuous operation limits (indicated on the unit data plate).
(3) Standardised EUROVENT conditions, water exchanger inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(4) Unit maximum current at 400 V, in non-continuous operation (indicated on the unit data plate).
(5) Unit maximum current at 360 V in non-continuous operation.