180
OVERVIEW OF THE PARAMETERS
INSTALLATION
Point name
Status
Default
Units
Text displayed*
Description
5
boil_th
From
-15.0 to
15.0
From 5.0
to 59.0
-9.9
14.2
°C
°F
OAT Boiler Threshold
OAT boiler threshold
(heat pumps only)
6
ehs_th
From -5.0
to 21.1
5.0
°C
Electric Stage OAT Threshold
Electric heating stage OAT threshold
From
-23.0 to
70.0
41.0
°F
7
both_sel
no/yes
no
-
Both HSM Control Selection
HSM Control
8
ehs_back
no/yes
no
-
1 Electric Stage For Backup
Electric heating stage for backup
9
ehs_pull
From 0 to
60
0
min
Electric Pull-Down Time
Electric pull-down time: It defines
the time between the unit start-up
and the determination of the pos-
sibility to start the electric heating
step
10
ehs_defr
no/yes
no
-
Fast EHS For Defrost
Fast electric heating used for de-
frosting purposes
* It depends on the selected language (English by default).
RESET CONFIG MENU – RESETCFG
Point name
Status
Default Units
Text displayed*
Description
1
COOLING RESET
Cooling reset parameters
2
oatcr_no
From -10.0
to 51.7
From -14.0
to 125.0
°C
°F
OAT Reset Missing Value
OAT reset missing value
3
oatcr_fu
From -10.0
to 51.7
From -14.0
to 125.0
°C
°F
OAT Complete Reset Value
OAT complete reset value
4
dt_cr_no
From 0 to
13.9
From 0 to
25.0
^C
^F
Reset Value Missing Delta T
Reset value missing Delta T
5
dt_cr_fu
From 0 to
13.9
From 0 to
25.0
^C
^F
Complete Reset Value Delta t
Complete reset value Delta t
6
I_cr_no
From 0 to 20
mA
Reset Missing Current Value
Reset missing current value
7
I_cr_fu
From 0 to 20
mA
Complete Reset Current Value
Complete reset current value
8
cr_deg
From -16.7
to 16.7
From -30.0
to 30.0
^C
^F
Cooling reset Deg. Value
Cooling reset Deg. value
9
HEATING RESET
Heating reset parameters
10
oathr_no
From -10.0
to 51.7
From -14.0
to 125.0
°C
°F
OAT Reset Missing Value
OAT reset missing value
11
oathr_fu
From -10.0
to 51.7
From -14.0
to 125.0
°C
°F
OAT Complete Reset Value
OAT complete reset value
12
dt_hr_no
From 0 to
13.9
From 0 to
25.0
^C
^F
Reset Value Missing Delta T
Reset value missing Delta T
13
dt_hr_fu
From 0 to
13.9
From 0 to
25.0
^C
^F
Complete Reset Value Delta t
Complete reset value Delta t
14
I_hr_no
From 0 to 20
mA
Reset Missing Current Value
Reset missing current value
15
I_hr_fu
From 0 to 20
mA
Complete Reset Current Value
Complete reset current value