124
INSTALLATION
INSTALLATION
2.9.1
Connection diagram
1
Brazed plate heat exchanger
2
Heat exchanger electric heating element
3
Shut-off valve
4
Filling unit
5
Air vent
6
Pressure gauge
7
Anti-vibration joints
8
Mesh filter
9
Expansion tank
10
Safety valve
11
Discharge valve
12
Pressure sensor
13
Pipe electric heating element (optional)
14
Circulation pump (single or double)
15
Non-return valve (if second pump is present)
16
Temperature probe
17
Backup tank (optional)
18
Water flow control valve (not required with variable
speed pump)
1
Brazed plate heat exchanger
2
Heat exchanger electric heating element
3
Shut-off valve
4
Filling unit
5
Air vent
6
Pressure gauge
7
Anti-vibration joints
8
Mesh filter
9
Expansion tank
10
Safety valve
11
Discharge valve
12
Flow Switch
13
Pipe electric heating element (optional)
14
Circulation pump (single or double)
15
Non-return valve (if second pump is present)
16
Temperature probe
17
Backup tank (optional)
18
Water flow control valve (not required with variable
speed pump)
NXC-NXH with hydronic module
NXC-NXH without hydronic module
2
1
13
13
13
13
16
13
14
15
10
11
8
3
4
3
3
3
Connections to be
made by the installer
18
3
3
7
7
6
6
5
5
T
16
17
T
11
11
9
P
12
P
12
NXC-NXH unit
2
1
13
13
13
13
16
13
14
15
10
8
3
4
3
3
3
Connections to be made by the installer
18
3
3
7
7
6
6
5
T
16
17
T
11
11
9
F
12
NXC-NXH unit
The water connections must be completed by installing:
− expansion tank if system water volume is higher than the maximum value listed in the tables in section "System water
content and flow rate"
− an appropriately sized technical water accumulation tank
− filling unit
− air vent valves in the piping highest points in addition to those already present on the equipment
− flexible elastic joints
− shut-off valves
− a by-pass valve between the device's delivery and return lines, in order to prevent freezing during the wintertime.