114
GENERAL INFORMATION
1.10
Cooling circuit and probe positioning
The cooling circuit is of the heat pump type with a refrigerant gas reversal cycle. The source fluid utilized is the external air, while
the utility fluid is water, with the possible inclusion of anti-freeze liquid.
In winter, the heat pump extracts thermal energy from the external air and releases it into the utility fluid heating it up, while
in summer
the cycle is inverted and the thermal energy is extracted from the water, that cools down, and is then released into the external
air.
Based on the type of system, the utility fluid is delivered to the fan coils, the air treatment unit, the radiant panels for
heating or cooling the rooms, or the boiler to produce domestic hot water.
8
1
9
10
2
11
3
7
6
5
4
J3
J6
J1
TE
J2
J4
J5
1
Compressor
2
Cycle reversal valve
3
Brazed plate heat exchanger
4
Receiver
5
Electronic expansion valve
6
Flow indicator
7
Dehydration filter
8
Finned coil
9
High pressure-switch
10
Safety valve
11
Safety valve
External
J1
Compressor discharge pressure sensor
J2
Compressor intake pressure sensor
J3
Suction temperature sensor
J4
Water return temperature sensor
J5
Water delivery temperature sensor
J6
Outdoor air temperature sensor
TE
Finned coil temperature sensor
Cooling circuit of NXH series devices
Содержание 20120391
Страница 93: ...93 PANORAMICA DEI PARAMETRI INSTALLAZIONE ...
Страница 169: ...169 ALARM CODES INSTALLATION ...
Страница 185: ...185 OVERVIEW OF THE PARAMETERS INSTALLATION ...
Страница 186: ......
Страница 187: ......