177
OVERVIEW OF THE PARAMETERS
INSTALLATION
SETPOINT MENU – SETPOINT
Point name
Status
Default
Units
Text displayed*
Description
1
csp1
From
-28.9 to
20.0
From
-20.0 to
68.0
7.0
44.6
°C
°F
Cooling Setpoint 1
Cooling setpoint 1
2
csp2
From
-28.9 to
20.0
From
-20.0 to
68.0
7.0
44.6
°C
°F
Cooling Setpoint 2
Cooling setpoint 2
3
hsp1
From 25.0
to 55.0
From 77.0
to 131.0
38.0
100.4
°C
°F
Heating Setpoint 1
Heating setpoint 1
4
hsp2
From 25.0
to 55.0
From 77.0
to 131.0
38.0
100.4
°C
°F
Heating Setpoint 2
Heating setpoint 2
5
ramp_sp
From 0.1
to 1.1
From 0.2
to 2.0
0.6
1.0
°C
°F
Heating Ramp Charging
Ramp charging
6
cauto_sp
From 3.9
to 50.0
From 39.0
to 122.0
23.9
75.0
°C
°F
Cool Switching Setpoint
Cool switching setpoint
7
hauto_sp
From 0 to
46.1
From 32.0
to 115.0
17.8
64.0
°C
°F
Heat Switching Setpoint
Heat switching setpoint
8
lim_sp1
From 0 to
100
100
%
Switch 1 Limit Setpoint
Switch 1 limit setpoint
9
lim_sp2
From 0 to
100
100
%
Switch 2 Limit Setpoint
Switch 2 limit setpoint
10
lim_sp3
From 0 to
100
100
%
Switch 3 Limit Setpoint
Switch 3 limit setpoint
11
min_sct
From 26.7
to 60.0
From 80.0
to 140.0
40.0
104.0
°C
°F
Desuperheater Min Sct
Desuperheater minimum saturated
condensing temperature