173
OVERVIEW OF THE PARAMETERS
INSTALLATION
8
HD_POS_A
-
%
Position A Piezometric Height
Piezometric height, circuit A
9
EXVPosA
-
%
EXV Position, Circuit A
EXV Position, circuit A
10
EXVNPosA
-
%
EXV next position, Circuit A
EXV next position, circuit A
11
RV_A
off/on
-
4-way Refrigerant Valve A
4-way refrigerant valve, circuit A:
Used to manage cooling/heating/
defrost operation (heat pumps)
12
CP_B1
off/on
-
Compressor B1 Output
Compressor B1 Status
13
CP_B2
off/on
-
Compressor B2 Output
Compressor B2 Status
14
FAN_B1LS
off/on
-
Fan output B1LS
Low speed fan B1 status
15
FAN_B1HS
off/on
-
Fan output B1HS
High speed fan B1 status
16
HD_POS_B
-
%
Position B Piezometric Height
Piezometric height, circuit B
17
EXVPosB
-
%
EXV Position, Circuit B
EXV Position, circuit B
18
EXVNPosB
-
%
EXV next position, Circuit B
EXV next position, circuit B
19
RV_B
off/on
-
4-way Refrigerant Valve B
4-way refrigerant valve, circuit B:
Used to manage cooling/heating/
defrost operation (heat pumps)
20
C_HEATER
off/on
-
Heater Drain Tray and Cooler
Water exchanger / Heater with
drain tray
21
BOILER
off/on
-
Boiler control
Boiler status
22
EHS_STEP
-
-
Electric Heating Stage
Electric heating steps
23
ALARM_R
off/on
-
Alarm Relay Status
Alarm relay status
24
RUN_R
off/on
-
Operating status
Unit Relay ON
25
OIL_VALV
off/on
-
Oil Valve Status
Oil valve status
* It depends on the selected language (English by default).
PUMP STATUS MENU – PUMPSTAT
Point name
Status
Units
Text displayed*
Description
1
CPUMP_1
off/on
-
Water Pump Control no.1
Water pump control no.1
2
CPUMP_2
off/on
-
Water Pump Control no.2
Water pump control no.2
3
ROT_PUMP
no/yes
-
Rotate pump now?
Water pump rotation
4
W_P_IN
-
kPa / PSI
Inlet Water Pressure
Inlet water pressure
5
W_P_OUT
-
kPa / PSI
Outlet Water Pressure
Outlet water pressure
6
WP_CALIB
no/yes
-
Water Pressure Calibration
Water pressure calibration
7
WP_OFFST
-
kPa / PSI
Water Pressure Compensation
Water pressure compensation
8
DP_FILTR
-
kPa / PSI
Water Pressure Filtering Delta
Water pressure filtering delta
9
WP_MIN
-
kPa / PSI
Water Min Pressure
Water minimum pressure
10
WAT_FLOW
-
l/s / GPS
Water Flow
Water flow status
11
CAPPOWER
-
kW
Effective Power Capacity
Effective power capacity
12
p_dt_spt
-
^C / ^F
Water DT setpoint
Water drain temperature setpoint
13
p_dp_spt
-
kPa / PSI
Water DP setpoint
Water drain pressure setpoint
14
drvp_pct
-
%
Pump Drive Percentage
Pump drive percentage
15
drvp_pwr
-
kW
Pump Drive Power
Pump drive power
16
drvp_i
-
A
Pump Drive Amp
Pump drive (A)
17
drvp_ver
xxx
-
Pump Drive Version
Pump drive version
* It depends on the selected language (English by default).
DC FREE COOLING STATUS MENU – FCOOL_ST
Point name
Status
Units
Text displayed*
Description
1
fc_oat
From 0 to 0
°C / °F
Free Cooling OAT
Free Cooling OAT
2
fc_lwt
From 0 to 0
°C / °F
FC Leaving Water Temp
Free Cooling LWT
3
fc_wloop
From 0 to 0
°C / °F
FC Water Circuit Temp
Free Cooling water circuit temper-
ature
4
m_fcool
no/yes
-
Active Free Cooling Mode
Free Cooling Mode - status
5
fc_cap
From 0 to 100
%
FC capacity
Free Cooling mode capacity
6
fc_fanst
From 0 to 7
-
FC Fan Stage
Number of fan stages in Free Cool-
ing
Содержание 20120391
Страница 93: ...93 PANORAMICA DEI PARAMETRI INSTALLAZIONE ...
Страница 169: ...169 ALARM CODES INSTALLATION ...
Страница 185: ...185 OVERVIEW OF THE PARAMETERS INSTALLATION ...
Страница 186: ......
Страница 187: ......