To program the UltraTWIN for
Example 3 BS3680 Weir
by using the
Quick
Setup
menu proceed as follows. If required access the
Program Mode
, key
in the
passcode
1997 and press
ENTER.
Using the ‘right’ arrow key, go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
QUESTION
OPTION
Application
3 = Flow
PMD Type
2 =
3680 Weir
3680 Flumes
1 = Rectangular
Calculation
1 = Absolute
No. of alarms
1 = 1 Alarm
Type alarm 1
1 = High
Alarm No.1
3 = Set to relay 3
Transducer (P1-101)
1 = dB Mach3
Volume units (P1-706)
5 = US Gallons
Time Units (P1-707)
2 = Per minute
Measurement units (P*104)
5 = inches
Empty level (P1-105)
40 inches
Minimum head (P1-703)
0.00 inches
Maximum head (P1-704)
16 inches
Totaliser Alloc. (P1-824)
1 = Point 1
Aux. Mode (P1-815)
7 = Totaliser
Aux Source (P1-816)
1 = Point 1
Totaliser multiplier (P1-823)
7 = *1,000
Approach dia. (Dim A) (P1-710)
0.70m
Throat dia. (Dim B) (P1-711)
0.50m
Throat length (Dim C) (P1-712)
1.00m
Programming is now complete, and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the UltraTWIN will return to
Run Mode
.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can
be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is
displayed, and entering new values to relay setpoints as required. Alternatively,
access the setpoints by the main menu system or directly accessing the parameters.