PULSAR MEASUREMENT
133
OPTIONS
DESCRIPTION
3 = General
Control
Control is based on the level in the vessel. All general
controls are used to assist each other (run at the same time)
and each
general control relay has its own “ON” and “OFF”
setpoints. Two setpoints are required, “ON” (P*2
1
3, 2
2
3, 2
3
3,
2
4
3, 2
5
3, 2
6
3) and “OFF” (P*2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4).
The
third parameter
for each relay determines the
assignment
or
condition
of the relay, where required.
P*212, P222, P232, P242, P252, 262 - Relay Alarm ID/Pump Group,
P*211, 221, 231, 241, 251, 261 = 1 (Time), or 3 (General Control)
This parameter has no function and will not be displayed.
P*211, 221, 231, 241, 251, 261 = 2 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Close
condition
(decrease level).
The
fourth parameter, fifth parameter
and
sixth parameter
are set to
determine the switch points, “
ON
” and “
OFF
” for the relay and where
required the order of start. See control function, table (P*211, 221, 231) for
further information.
P*213, P223, P233, P243, P253 Relay Setpoint 1
P*211, 221, 231, 241, 251, 261 =1 (Time)
This parameter determines the “Time Period” that the relay will remain “ON”.
Relay Setpoints are entered in Minutes.
See the appropriate relay Function tables (
P*211, 221, 231, 241, 251, 261
)
for further information.
P*211, 221, 231, 241, 251, 261 = 2 (Step Time)
Relay Setpoint 1 is entered in values of Measurement Units (P*104)
See the appropriate relay function tables (
P*211, 221, 231, 241, 251, 261
)
for further information.