P*214, 224, 234, 244, 254, 264
–
Relay Setpoint 2
This parameter determines the ‘
OFF
’ point
of the pump.
The
sixth parameter
will determine the
service ratio
that will be used to
switch the pump, when
pump duty
selected is a Service Ratio duty.
P*210, 220, 230, 240, 250 = 6, 7 or 9 (Service ratio)
P*215, 225, 235, 245, 255, 265
–
Relay Setpoint 3
This parameter determines the Service Ratio in values of %. See the
appropriate
pump duty
function, table (
P*211, 221, 231, 241, 251, 261
),
for further information.
P*219, 229, 239, 249, 259, 269
–
Relay Max Rate
This parameter will allow a
pump
to be
switched
at a pre-determined
Rate
of change of Level
, irrespective of the “ON” level setpoint P213, 223, 233
,
243, 253, 263
. Once a pump relay has been switched “
ON
” by the pre
-
determined
Rate of Change
, it will remain energised until the level reaches
the “
OFF
” level setpoint
P*214, 224, 234, 244, 254, 264
.
Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level)
values.