PULSAR MEASUREMENT
67
APPLICATION
NO. OF
PUMPS
PUMP
NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Up
One
Pump 1
50%
20%
Pump Up
Two
Pump 1
Pump 2
50%
30%
20%
20%
Pump Up
Three
Pump 1
Pump 2
Pump 3
50%
40%
30%
20%
20%
20%
Pump Up
Four
Pump 1
Pump 2
Pump 3
Pump 4
60%
50%
40%
30%
20%
20%
20%
20%
Pump Up
Five
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
60%
50%
40%
30%
75%
20%
20%
20%
20%
20%
Pump Up
Six
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
40%
50%
60%
70%
75%
80%
20%
20%
20%
20%
20%
20%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
Important Notice
When using the Quick Setup Menu relays will be allocated to the point of
measurement you are currently setting up and the availability of relays will
depend on the number of relays used when setting up the previous point
of measurement via the Quick Setup Menu for that point.