PULSAR MEASUREMENT
85
To program the UltraTWIN for
Example 1 V-Notch Weir
by using the
Quick
Setup
menu proceed as follows. If required access the
Program Mode
, key
in the
passcode
1997 and press
ENTER.
Using the ‘right’ arrow key, go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
Programming is now complete, and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the UltraTWIN will return to
Run Mode
.
QUESTION
OPTION
Application
3 = Flow
PMD Type
1 = Exponent
Exponent
6 = V-Notch
Calculation
2 = Ratiometric
No. of alarms
0 = No alarms
Xducer
1 = dB Mach3
Volume units (P*706)
6 = Mil USG
Time units (P*707)
4 = day
Measurement units (P*104)
5 = inches
Empty Level (P*105)
40 inches
Minimum head (P*703)
0.00 inches
Maximum head (P*704)
15 inches
Totaliser Alloc. (P*824)
1 = On
Aux. Mode (P*815)
2 = Level
Aux Source (P*816)
0 = Off
Totaliser multiplier
1 = /1,000
Max flow
2.2