![Pulsar UltraTWIN Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/pulsar/ultratwin/ultratwin_instruction-manual_1624516065.webp)
PULSAR MEASUREMENT
65
PARAMETER
DEFAULT
DESCRIPTION
P830 mA Out Range 2 = 4 to 20mA
Determines the mA output
range. 0 = Off, 1 = 0 to 20mA,
2 = 4 to 20mA
, 3 = 20 to 0mA,
4 = 20 to 4mA.
P870 Fill Damping
32.8084 ft/min
Rate of maximum fill rate (set
above the actual fill rate of the
vessel).
P871 Empty
Damping
32.8084 ft/min
Rate of maximum empty rate
(set above the actual rate of
the vessel).
The default values used for determining the
relay setpoints
, when setting
Alarm
and
Pump
relays, via the
Quick Setup
menu are entered as a % of
span and are as follows.
APPLICATION
NO. OF
PUMPS
PUMP
NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
80%
20%
Pump Down
Two
Pump 1
Pump 2
80%
70%
20%
20%
Pump Down
Three
Pump 1
Pump 2
Pump 3
80%
70%
60%
20%
20%
20%
Pump Down
Four
Pump 1
Pump 2
Pump 3
Pump 4
80%
70%
60%
50%
20%
20%
20%
20%
Pump Down
Five
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%
Pump Down
Six
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
80%
70%
60%
50%
40%
30%
20%
20%
20%
20%
20%
20%
Содержание UltraTWIN
Страница 1: ...UltraTWIN UL Instruction Manual...
Страница 2: ...2...
Страница 15: ...PULSAR MEASUREMENT 15 EU Certificate of Conformity...
Страница 24: ...ULTRATWIN UL INSTRUCTION MANUAL 24 Fascia Mount The terminal details are as illustrated below...
Страница 213: ...PULSAR MEASUREMENT 213 NOTES...