PULSAR MEASUREMENT
143
Input Function
Individual inputs can be configured for any one of a number of
Functions
as
determined by
P*373, 376, 379, 382, 385, 388, 391
these functions are as
follows:
OPTIONS
DESCRIPTION
1 = Device Fail:
Input will provide a signal indicating a “failure” or the
presence of a “run” signal from the device. When
using digital inputs to detect a “run” condition the
input is assumed to be in its operational status until
the expiry of
P*304 Input Delay
which is used to
determine the delay time that occurs from the time
that the device is called to “run” and the digital input
providing a signal appropriate to its operational
status.
2 = Duty:
Input will provide a signal to manually select the lead
device.
3 = Override ON:
Input will provide a signal to override all selected
pump setpoints “ON”.
4 = Override OFF:
Input will provide a signal to override all selected
pump setpoints “OFF”.
5 = Reset:
Input will provide a signal to reset all Device Fail
signals.
6 = Inhibit Measurement
Input will provide a signal to inhibit the measurement
of the point it is allocated to.