P*212, 222, 232, 242, 252, 262 Relay Alarm ID
When P*211, 221, 231, 241, 251, 261 = 7 (Device Alarm)
This parameter defines which
digital input
, the
alarm
should respond to, as
follows.
OPTION
DESCRIPTION
SETPOINTS
1 = Fail Input 1 (Default)
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 1
.
None
2 = Fail Input 2
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 2
.
None
3 = Fail Input 3
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 3
.
None
4 = Fail Input 4
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 4
.
None
5 = Fail Input 5
(Wall Mount Only)
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 5
.
None
6 = Fail Input 6
(Wall Mount Only)
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 6
.
None
7 = Fail Input 7
(Wall Mount Only)
Relay goes “
ON
” when a
device
fail signal
is detected on
digital
input 7
.
None