PULSAR MEASUREMENT
151
P*373, 376, 379, 382, 385, 388, 391 Function
This parameter will set the function of the digital Input.
OPTIONS
DESCRIPTION
1 = Device Fail
(Default Input 1 to 6)
Digital input is used to Fail, (put out of service), a device
connected to the relay specified in
P*374, 377, 380,
383, 386, 389, 392 Assignment
2 = Duty
Digital input is used to select the device, (pump),
connected to the relay specified in
P*374, 377, 380,
383, 386, 389, 392 Assignment
as the current duty
device (pump).
3 = Override “ON”
Digital input is used to provide a signal to activate an
Override “ON”
condition of pumps as determined by
P*302 Override Delay,
P*303 Min. Override
and
P*306 Override Level
.
4 = Override “OFF”
Digital input is used to provide a signal to activate an
Override “OFF”
condition of pumps after the expiry of
the delay time as determined by
P*302 Override Delay
.
5 = Reset.
(Wall Mount Input 4 only)
(Fascia Mount Input 7)
Input is used to
Reset
all
Device Fail
conditions.
Alternatively, the
+/-
key can be used, whilst in RUN, to
Reset
any
Device Fail.
6 = Inhibit Measurement
Input is used to inhibit the measurement of the point it
is allocated too as specified by
P*374, 377, 380, 383,
386, 389, 392
(Assignment)
.
P*374, 374, 380, 383, 386, 389, 392 Assignment
When P*373, 376, 379, 382, 385, 388, 391
=
1
(Device Fail
) or
2
(
Duty
)
This parameter assigns the digital input to the appropriate device relay that
the
Function
. (
P*373, 376, 379, 382, 385, 388, 391
), is to be applied.
OPTIONS
DESCRIPTION
0 = None (Default)
Digital Input is not assigned to any relay
1 = Relay 1
Digital input is assigned to Device connected to Relay 1.
2 = Relay 2
Digital input is assigned to Device connected to Relay 2.
3 = Relay 3
Digital input is assigned to Device connected to Relay 3.
4 = Relay 4
Digital input is assigned to Device connected to Relay 4.
5 = Relay 5
Digital input is assigned to Device connected to Relay 5.
6 = Relay 6
Digital input is assigned to Device connected to Relay 6.
7 = All
Digital input is assigned to All relays with a device connected.