PULSAR MEASUREMENT
209
P*981 Increment
By
default
, simulation mode will move by
0.328 feet
steps in manual
simulation and by
0.328 feet/min
in automatic simulation. Altering the
increment can change this value.
P*982 Rate
In automatic mode, the rate at which the level will move up and down, is
determined by distance,
P*981 Increment
and the time,
P*982 Rate
which
by
default
is set to
1min
and can be changed as required. To increase the
rate at which the level moves increase the
Increment (P*981)
or decrease
the
Rate (P*982)
. To decrease the rate at which the level moves decrease
the
Increment (P*981)
or increase the
Rate (P*982)
.
P*983 Start Level
When using automatic simulation this parameter can be used to pre-
determine the point at which the simulated level will start at and return to.
This can be used to simulate the lowest point to which the level would
normally operate.
P*984 Inc. Change
When using automatic simulation, you can incrementally increase or
decrease the rate whilst running simulation. The rate is increased /decreased
incrementally by the value
P*984 (Incremental Change)
by using the
“
decimal point
”
key to
increase
and the
“
plus/minus
” key to
decrease
the
rate of change.
Default = 0.328 feet
Hardware
P1 and P2
P*990 Self Test
If you enter 1 for this parameter, then the unit will perform a self-test. This
will confirm that the various parts of the circuitry are working correctly. You
will see confirmation messages that the clock and the EEPROM are working
correctly, and error messages for any parts that fail.