ULTRATWIN (UL)
INSTRUCTION MANUAL
130
PUMP DUTY
DESCRIPTION
8 =
F
irst
O
n
F
irst
O
ff
Alternate duty assist
The first pump switched on is the first pump to
be switched off, etc. regardless of the set points,
so the setpoints are dynamically changed to
enable this.
9 = Service Ratio Standby
When a service ratio duty is being used, on all
other pumps in use, the standby pump can be
started on a ratio basis only, when it will assume
the setpoints of the next pump to start. The third
setpoint (P*2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
5
5, 2
6
5) is used
to set the service ratio.
10 = Two Pump Sets
There are four pumps. Two rotate their start-up
sequence with each other. If the two pumps
cannot keep up, the level rise to the setpoints of
the other two pumps which take over and rotate
their sequence with each other.
The
third parameter
for each relay determines the pump group. You can
have two groups of pumps, and all similar duties within that group will
operate together.
P*212, 222, 232, 242, 252, 262
–
Relay Pump Group
By
default
, all pump groups are set to
1
, but if you want to have another
group, then set this parameter to 2, for each pump relay that should operate
together as part of a second group.
The
fourth parameter
and the
fifth parameter
for each relay set the
pump
“
ON
” and “
OFF
” points, which are entered in
Measurement units P*104
.
For
pump down
the “
ON
” is set
higher than
“
OFF
”. For
pump up
then “
ON
”
is set
lower than
“
OFF
”. See the appropriate
pump duty,
function
table
(
P*212, 222, 232, 242, 252, 262
) for further information.
P*213, 223, 233, 243, 253, 263
–
Relay Setpoint 1
This parameter determines the ‘
ON
’ point of the pump.
Important Notice
The pumps are started and stopped at the “ON” and “OFF” setpoints. To
pump down
(reduce level) then set “ON” higher than “OFF”. To
pump up
(increase level) then set “ON” lower than “OFF”.
Содержание UltraTWIN