ULTRATWIN (UL)
INSTRUCTION MANUAL
194
P*882 Process Filter
This parameter
determines the number of ‘cycles’ that will be taken before a
change in level is processed and the display updated.
OPTION
DESCRIPTION
1 = Fast
level will be updated every cycle
2 = Medium
level will be updated every 8 cycles
3 = Slow (Default)
level will be updated every 16 cycles
P*884 Peak Percentage
This parameter is used if you choose a solids application,
P*102 Material =
2 (Solids)
, where there maybe angles of repose on the material, and can be
used to determine where in the returned echo the displayed level is
.
Default = 50%
Echo Processing Parameters
P1 and P2
Transducer 1 Status
P*900 Transducer Status 1
This parameter shows the current state of the transducer. The value means
the following:
OPTION
DESCRIPTION
0= OK
Transducer working correctly.
1= Disabled
Transducer is not being used (mA input is being
used instead, so P*101 = 1)
2= Stuck High
Indicates that the power and signal lines on the
transducer terminals are crossed over, or the signal
line is shorted to earth.
3= Not Found
No transducer is detected.
P*901 Echo Confidence 1
This parameter displays the most recent echo confidence from the
transducer. It is useful to help find the best mounting location for the
transducer, where you should aim to get the highest figure. It is a
percentage of confidence that the echo reporting the level is the correct
one.