PULSAR MEASUREMENT
71
The display will show the level in the sump and the mA output will be
representative of level where 4mA = empty level (0%) and 20mA = 10.0 feet
(100%).
To program the UltraTWIN for
Example 3 Reservoir Control (pump up) by
using the
Quick Setup
menu proceed as follows. If required access the
Program Mode
and key in the
passcode
1997
and press
ENTER
Using the ‘right arrow key, go to
Quick Setup
menu press
ENTER
and as
prompted, by the questions, select the relevant option and
ENTER
.
QUESTION
OPTION
Application
2 Pump
Level/Pump Up/Down
2 = Pump Up
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
No. of alarms
1 = 1 Alarm
Type Alarm 1
2 = Low
Alarm No. 1
3 = Set to Relay 3
Xducer (P101)
2 = dB6
Measurement units (P*104) 4 = feet
Empty Level (P*105)
11.0 feet
Span (P*106)
10.0 feet
Programming is now complete, and the unit can be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the UltraTWIN will return to the
Run Mode
.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed, and
entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either
by the main menu system or directly via parameter number and changed,
as necessary.