P*822 Totaliser Decimal Places
This parameter determines the number of decimal places in the totaliser
during run mode. It can be set between 1 and 3.
Default = 2
P*823 Totaliser Multiplication Factor
This parameter determines the number of decimal places in the totaliser
during run mode. It can be set between 1 and 3.
Default = 2
Use this parameter if the totaliser increments by to large or small amount,
enter the factor by which the actual flow rate is multiplied by before
incrementing the totaliser.
Example:
If flowrate is being calculated and displayed in ltrs/second and it is
desired to increment the totaliser in cubic metres select 7 = *1000.
When viewing, the totaliser display will state, “Units are: L*1000”, and the
totaliser will be incremented every 1000 litres. The options are:
OPTION
DESCRIPTION
1 = 1/1000
Totaliser will increment every 1/1000
th
units of flow
2 = 1/100
Totaliser will increment every 1/100
th
units of flow
3 = 1/10
Totaliser will increment every 1/10
th
units of flow
4 = *1 (Default)
Totaliser will increment every 1 units of flow
5 = 10
Totaliser will increment every 10 units of flow
6 = 100
Totaliser will increment every 100 units of flow
7 = 1,000
Totaliser will increment every 1000 units of flow
8 = 10,000
Totaliser will increment every 10,000 units of flow
9 = 100,000
Totaliser will increment every 100,000 units of flow
10 = 1,000,000
Totaliser will increment every 1,000,000 units of flow