FINS commands
Section 3-4
69
The CJ1W-MCH72 responds with these codes:
/i
If the response code is 0000, the cyclic area number specified in
area_code
is
configured to exchange data between the PLC CPU and the CJ1W-MCH72.
area_code
•
0100..0107 for PLC output area (8 areas available)
•
8100..8107 for PLC input area (8 areas available)
start_address
0000
byte_count
0008
plc_area
•
01 (CIO)
•
03 (DM)
•
04 (WR)
•
05 (HR)
•
08..14 (EM bank 0..C)
plc_start
Start address in PLC memory
(Validity depends on
plc_area
)
tj_area
•
00 (VR 16-bit signed integer)
•
01 (VR 32-bit floating point)
•
02 (IN or OP array, depending on direction)
•
03 (AIN or AOUT array, depending on direction)
•
04 (Axis Status array, only valid if direction is PLC input)
tj_start
Start address in CJ1W-MCH72 memory
(Validity depends on
tj_area
)
total_items
Total items (words and dwords) to transfer
(Validity depends on
plc_area
and
tj_area
)
Condition
Response code
(hex)
Description
All elements valid
0000
OK
area_code
invalid
1101
No area type
start_address
invalid
1103
Address range designation error
byte_count
invalid
1104
Address out of range
plc_area
, plc_start,
tj_area
or
tj_start
invalid
110C
Other parameter error
total_items
greater than
2000 words
2103
Data has not been registered
Parameter
Values (hex)
Note
The first 16 entries in the IN array cannot be addressed in the memory
mapping. These first 16 entries map to the inputs available on the I/O
connector.
Содержание SYSMAC CJ Series
Страница 2: ......
Страница 70: ...Specifications Section 2 4 58...
Страница 84: ...FINS commands Section 3 4 72...
Страница 148: ...All BASIC commands Section 4 2 136 AXIS 1 AXIS 0...
Страница 277: ...Section 265 SECTION 5 Examples This chapter gives 2 categories of examples and tips How to s Practical examples...
Страница 370: ...Section 358...