69
F3SG-SR
User’s Manual
Chapter
2
Muting
System Operation and Functions
E
Installation Example 2 of Standard Muting Mode (Using Four Muting Sensors)
This installation example uses four through-beam type photoelectric sensors as muting sensors.
The use of four muting sensors is useful when the length of the workpieces is constant or longer, and
the entrance and exit have enough space. Muting can be activated from both directions in the
arrangement as shown below.
1.
Before a workpiece passes through
All muting sensors are turned OFF and the safety function of the F3SG-SR is enabled.
2.
MUTING started
When the muting sensors A1 and B1 are turned ON in this order, MUTING starts. In this state, the
safety function of F3SG-SR is disabled.
A1
B1
F3SG-SR
B2
A2
Workpiece
V
Workpiece
V
D3
L
d2
d2
Hazardous zone
L: Length of workpiece
d2: Maximum distances required for the muting sensor to keep the muting function enabled
D3: Minimum distance required for the muting sensor to keep the muting function enabled
A1
F3SG-SR
A2
Workpiece
Hazardous zone
B1
B2
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...