107
F3SG-SR
User’s Manual
Chapter
2
Warning Zone
System Operation and Functions
E
2-18-2. Factory Default Setting
Warning Zone is disabled.
2-18-3. Setting with Intelligent Tap
The user cannot make any changes to the settings of this function by the Intelligent Tap.
2-18-4. Setting with SD Manager 3
The user can make changes to the settings of this function by the SD Manager 3.
If you want to output the beam state of the warning zone, set the output operation mode of the Auxiliary
Output to Warning Zone Information.
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Function
Initial value
Configurable value or numerical range
Warning Zone
Disable
Disable/Enable from upper/Enable from lower
Zone setting
None
Any beam from top beam/any beam from
bottom beam