4-4-3-3. Intelligent Tap Log
This function can be used only when the Intelligent Tap is connected to a PC. This function can be
used regardless of whether or not the F3SG-SR is connected with the Intelligent Tap.
Select [Intelligent Tap Log] from the [Maintenance Information] list in the [Menu] window.
The screen below is displayed. Click an error item you want to view and the cause and measures of the
error is displayed.
•
Intelligent Tap.
•
Refer to 2-26-7. Intelligent Tap Log for more information on the accumulated power-on time.
Logs of past 50 errors are saved in the Intelligent Tap log.
No.
Function
Description
1
Intelligent tap log
Error code, error details, and the accumulated power-on time when the error occurred are
displayed in order from the newest log.
2
Error details indication
By clicking each log, the details, cause, and countermeasures about the log are displayed.
3
Maintenance information
saving
Saves error and warning logs, Intelligent Tap log, power-on time, accumulated power-on
time, load switching frequency and accumulated load switching frequency as a .csv file.
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...