Troubleshooting
F3SG-SR
User’s Manual
Appendix
Communication
error in Backup
X
X
1E
The communication lines or other lines may be short-circuited
or broken.
Check the cables for cascading or extension cables.
If the wiring is extended with cables other than specified, the
cables used for extension may not have performance
equivalent or greater than the specified cables. Use cables
with the same performance or more than the specified cables.
Effect of noise may be excessive.
If other devices using the same power supply generate noise, do
not share the same power supply with other devices, and use a
separate power supply exclusively for the safety components.
The inductive noise tends to be induced especially if the power
supply line of the machine guarded and the power supply line of
the Intelligent Tap are arranged in parallel.
Arrange the exclusive power supply near the Intelligent Tap or
lay the power supply line of the Intelligent Tap away from the
power supply line of the machine guarded.
If the power supply for the Intelligent Tap is located near the
power supply of the machine guarded and it shares the same
grounding wire, it is subject to the influence of common mode
noise.
Separate the grounding point or use it as the exclusive ground.
5-4-4. Functional Earth Connection
The internal circuit of the Intelligent Tap may be defective.
Replace the Intelligent Tap.
Communication
error in
Restoration
X
X
1F
The communication lines or other lines may be short-circuited or
broken.
Check the cables for cascading or extension cables.
If the wiring is extended with cables other than specified, the
cables used for extension may not have performance equivalent
or greater than the specified cables. Use cables with the same
performance or more than the specified cables.
Effect of noise may be excessive.
If other devices using the same power supply generate noise, do
not share the same power supply with other devices, and use a
separate power supply exclusively for the safety components.
The inductive noise tends to be induced especially if the power
supply line of the machine guarded and the power supply line of
the Intelligent Tap are arranged in parallel.
Arrange the exclusive power supply near the Intelligent Tap or
lay the power supply line of the Intelligent Tap away from the
power supply line of the machine guarded.
If the power supply for the Intelligent Tap is located near the
power supply of the machine guarded and it shares the same
grounding wire, it is subject to the influence of common mode
noise.
Separate the grounding point or use it as the exclusive ground.
5-4-4. Functional Earth Connection
The internal circuit of the Intelligent Tap may be defective.
Replace the Intelligent Tap.
Description
Checking by
Error code
(HEX)*
Cause and measures
Indicator
SD Manager 3/
SD Manager 3
Mobile APP
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...