226
Chapter
4
Monitoring with SD Manager 3
F3SG-SR
User’s Manual
Setting with SD Manager 3
4.
Check the analysis data (10) to see if there is any unnecessary data.
It is possible to delete unnecessary data by selecting the data on the screen and pressing the [Delete]
key. The table (7) and chart (11) will be updated each time analysis data is deleted.
If you have deleted analysis data accidentally, click the [Retrieve log] button again to recall it.
5.
Select a desired standard deviation range (9) from the pull-down menu.
6.
The flowchart below shows an example to optimize setting parameters of muting input time difference
based on analysis data.
7.
Adjusting the T1 Min and T1 Max closer to the A.D. Min and Max allows the user to keep the
productivity and improve the safety.
The following operations in Step 7 are unnecessary if the T1 Min and T1 Max are fairly close to the A.D. Min and Max.
If you change T1 Min and T1 Max, make sure that these values satisfies "T1 Min < A.D. Min < A.D. Max < T1 Max".
Is judgment in chart (7) red?
No
Yes
Is the range of A.D.
between T1 Min and T1 Max?
No
Optimizing muting setting parameters
Is judgment in chart (7) yellow?
No
Yes
Yes
Judgment in chart (7) is green.
The muting is possible with current
settings and installation.
Go to Step 7 to keep the
productivity and improve the safety
in the current conditions.
There is analysis data out of the range of A.D. Min to Max.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Select another standard deviation range value.
The range of A.D. Min to Max is out of the range T1 min to T1 max.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Select another standard deviation range value.
3) Change T1min and T1max on the muting time information setting
screen.
Analysis data is out of the range of T1 Min to T1 Max, resulting in a
muting sequence error.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Change T1min/T1max value in Muting setting screen.
3) Change T1min and T1max values on the muting time information
setting screen.
4) Change installation conditions and retrieve logs again.
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...