Muting
F3SG-SR
User’s Manual
System Operation and Functions
Standard Muting mode
Exit-Only Muting mode
Position Detection Muting mode
Dynamic Muting
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Setting the muting time limit to infinite may cause a failure of the muting sensors to go undetected, resulting in the F3SG-SR
in an unintended MUTING state. Conduct risk assessment analysis thoroughly before enabling this setting.
Setting the muting input time limit value (maximum) to infinite may cause a failure of the muting sensors to go
undetected, resulting in a failure of disabling the MUTING state. Conduct risk assessment analysis thoroughly before
enabling this setting.
Dynamic Muting can be used in conjunction with any of Standard, Exit-Only and Position Detection Muting modes.
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 20 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 4 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 4 s in 0.1-s increments
T4: Muting end wait time
1 s
0.1 to 20 s in 0.1-s increments
T5: Exit-only muting delay time
4 s
4 to 20 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
max
: Muting input time limit value(maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption
0.1 s
0.1 to 4 s in 0.1-s increments
Function
Initial value
Configurable value or numerical range
Dynamic muting
Disable
Enable/Disable
Dynamic muting measurement time
3 s
1 to 25 s in 0.1-s increments
Number of dynamic muting allowable beams
1
0 to 5 in 1-beam increments
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...