210
Chapter
4
Changing Settings with SD Manager 3
F3SG-SR
User’s Manual
Setting with SD Manager 3
If using this function together with other functions, make settings taking the condition of adjacent zones into account.
For more information on zone adjacency conditions, refer to 2-19. Setting Zone Adjacency Conditions.
When changing the settings is complete, confirm the settings and write the configuration to the F3SG-SR.
To enable the written configuration, refer to 4-2-7-3. Writing Configuration into Intelligent Tap.
When connecting the Intelligent Tap to a F3SG-SR and trying to return the F3SG-SR to [Detecting], follow step 4 of
4-1-3-2. Connection Procedure When Using USB Connector to restart the F3SG-SR and Intelligent Tap, or click the
[Monitor]
button.
No.
Function name
Description
Initial
value
Configurable value or
numerical range
1
Muting Time
Information
Enter values of Muting-related time limits.
For the Muting time input time limit and the Muting time limit,
setting the value to zero means the time limit is infinite.
-
-
Standard muting
T1min: Muting input time limit
(Min. value)
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 20 s (in 0.1 s
increments)
Exit-only muting
T1min: Muting input time limit
(Min. value)
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 600 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 4 s (in 0.1 s
increments)
T4: Muting end waiting time
1 s
0.1 to 20 s (in 0.1 s
increments)
T5: Exit-only muting delay time
4 s
4 to 20 s (in 0.1 s
increments)
Position detection muting
T1max: Muting input time limit
(Max. value)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
T2: Muting time limit
60 s
1 to 600 s (in 1 s
increments)/infinite
T3: Maximum allowable
muting signal interruption
0.1 s
0.1 to 4 s (in 0.1 s
increments)
2
Check installation
position
Reflects the Muting Time Information settings to the timing
chart shown in the left side of the screen, and allows data entry
to the Input Information fields.
-
-
3
Input Information
Enter information about the work-piece.
-
-
4
Diagnosis of
installation
condition
It is diagnosed and displayed if the setting condition is
appropriate.
-
-
5
Evaluate
Checks if the muting with the entered settings is possible.
-
-
6
Installation
diagram and
Timing chart
Shows the positions and timing chart of a work-piece, the
F3SG-SR and muting sensors. You can also make settings to
the muting time information by editing the values in the timing
chart directly.
-
-
7
Close
Finishes the setting process of muting time information, and
returns to muting setting.
-
-
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...