WFDEN Vane-type Waterflow Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of waterflow detectors. Purchasers who install waterflow detectors for use 

by others must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning. Follow only those instructions that 

apply to the model you are installing.

CAUTION

The model WFDEN is a vane-type waterflow detector for use in wet-pipe fire sprin-

kler systems only. Vane-type waterflow detectors shall not be used as the sole initiat-

ing device in both deluge and preaction systems; waterflow detectors used in these 

types of systems may result in an unintended discharge caused by a surge, trapped air 

or a short retard time.

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water-filled pipes in fire sprinkler systems. 

Waterflow in the pipe deflects a vane, which produces a switched output, usually af-

ter a specified delay. All WFDENs have a pneumatically controlled mechanical delay 

mechanism. Delays do NOT accumulate; they reset if the flow of water stops or drops 

below minimum triggering flow rate before the entire delay has elapsed. 
All switches actuate on a sustained flow of water greater than the maximum specified 

in Table 1, but will not activate if the flow rate is less than the minimum specified in 

Table 1.
This Safe Signal installation manual covers the following waterflow detectors for fire 

sprinkler/fire alarm applications.

TABLE 1. 

VdS

LPCB

Model 

Number

DN Ref.

Pipe Size 

mm (in)

Nominal 

Pipe O.D. 

(mm)

Wall 

Thickness 

(mm)

Triggering 

Flow Rate 

(liters/min)

Nominal 

Pipe O.D. 

(mm)

Wall Thickness

(mm)

WFD20EN

50 (2)

60.3

2.3/2.9

47

60.3

3.6

WFD25EN

66 (2,5)

76.1

2.6/2.9

49

76.0

3.6

WFD30EN

80 (3)

88.9

2.9/3.2

47

88.8

4.0

WFD40EN

100 (4)

114.3

3.2/3.6

53

114.1

4.5

WFD60EN

150 (6)

168.3

4.0/4.5

55

165.1

5.0

WFD80EN

200 (8)

219.1

4.5/5.9

64

219.1

6.3

SPECIFICATIONS

Contact Ratings: 

10 A @ 125/250 VAC

~

; 2.5 A @ 24 VDC  

 

 

EC–certificate Number: 0786-CPR-40299

Triggering Flow Rate: 

Refer to Table 1  

 

 

 

 

EN12259–5

Static Pressure Rating (maximum): 

17.25 bar (250 psi) (1725 KPa); 16 bar (VdS) 

 

 

VDS Certificate Number: G 415003

Operating Temperature Ranges: 

0°C to 68°C (32°F to 155°F)

Compatible Pipe: 

Steel Water Pipe (Refer to Table 1)

Shipping Weight: 

3 to 6 lbs (according to size)

Enclosure Rating: 

Nema4/IP54

STEEL PIPE COMPATIBILITY

CAUTION

Do not use any of the WFDEN models on copper pipe. The clamping forces of the 

mounting bolts may collapse the pipe sufficiently to prevent the detector from func-

tioning properly.
Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow 

detector. Incompatibility between the dissimilar metals causes bimetallic corrosion.

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with national codes 

of practice and the requirements of the authority having jurisdiction.
NOTE: Installation methods other than those listed in this installation manual may 

prevent the device from reporting the flow of water in the event the associated fire 

sprinkler system is activated by a fire. Safe Signal is not responsible for devices that 

have been improperly installed, tested or maintained.
1.   Mount the detector where there is adequate clearance for installation and re-

moval and a clear view of it for inspections. See Figure 1 for mounting dimen-

sions.

2.   Locate the unit 1.8 – 2.1 meters above the floor to protect from accidental dam-

age.

3.   On horizontal runs, the detector must be positioned on the top of the pipe, not 

on the side or below. Do not mount it upside down because condensation may 

collect in the housing and impair the operation of the detector. For vertical flow 

applications, mount detector on pipe through which water flows upward.  Oth-

erwise, the unit may not operate properly. 

4.   Mount detector at least 15 cm from a fitting that changes the direction of the 

waterflow, or no closer than 61 cm from a valve or drain.

5.   BE SURE DIRECTION-OF-FLOW ARROW AND DIRECTIONAL COVER 

MATCHES ACTUAL DIRECTION OF FLOW IN THE PIPE. See Figure 6.

MOUNTING INSTRUCTIONS

1.  Drain the pipe.
2.   Cut a hole in the pipe in the desired location. Center the hole on the pipe as 

shown in Figure 2, and be sure the hole is perpendicular to the center of the 

pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the 

bit from slipping. If the hole is off center, the vane will bind against the inside 

wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See 

Table 2 for hole size. 

CAUTION

When drilling the hole with a hole saw, make certain that center of hole saw cut does 

not remain in pipe.

I56-4051-F

  

I56-4051-F 

 

 4/21