2-60
AFP-400 Installation
PN
50253
:
A2 03/12/96
SLC Wiring with CMX Control Modules
When an MPS-400 Notification Appliance Circuit supplies power to CMX mod-
ules:
1) The CMX module outputs are coded if the MPS-400 Notification Appliance
Circuit is coded.
2) Program the MPS-400 Notification Appliance Circuit for general alarm.
3) Terminate the power feed to the CMX module with a 2.2K ELR (P/N R-2.2K)
or make the power feed a return to the MPS-400 NAC terminals 3 and 4).
The wiring diagram shows an NFPA Style Z Notification Appliance Circuit
(all circuits are supervised and power-limited) using a CMX module. The
following table contains SLC wiring connections to the MPS-400 and CPU-400 as
shown in the wiring diagram.
Module
Connect...
MPS-400
24V (+) to TB* terminal 1
24V () to TB* terminal 2
* NAC TB7, TB8, TB9, or TB10
CPU-400
SLC (+) to TB5-1
SLC () to TB5-3
Do not loop wiring under
any terminals. Break wire
run to maintain supervi-
sion.
ELR End-of-Line
Resistor 47K, 1/2-watt
part number
SSD A2143-00
(N-ELR in Canada)
CMX
CMX
ELR
(see
note)
Refer to Device Compat-
ibility Document 15378
for compatible notifica-
tion appliances.
NFPA Style Y Notification Appliance Circuit
Style Z Circuits
24 VDC Notification
Appliances
MPS-400
CPU-400
Typical Style Z Wiring
Diagram
MPS-400 and CPU-400 SLC Connections
Return
(optional
for Style Y)
ELR
(see
note)
2.2K ELR
P/N R-2.2K
to next device on
SLC loop
+