AFP-400 Installation
PN 50253:A2 03/12/96
E-9
Using the CRT-2 for Alter Status, continued
This option lets you change the alarm and prealarm levels of any address-
able detector in the system. To do so, follow these steps.
1) From the Alter Status menu, select option 2,
Alarm/Prealarm.
2 Enter the address of the detector you wish to change.
For example: Change alarm and prealarm levels for detector 102
.
Change Alarm and
Prealarm levels
STATUS CHANGE Alarm/Prealarm level 09:53A Wed 08/02/95
D102 sens. at level 5, Prealarm at level 3, Enter AxPx to change, Esc. to Abort
D102 now set at new Alarm level 5 and new Pre-alarm level 2
Det. Alarm/Prealarm level, type address D(nnn), then Enter
STATUS CHANGE Alarm/Prealarm level 09:53A Wed 08/02/95
2 ENTER
D 1 0 2
ENTER
Press...
and the CRT-2 displays...
and the CRT-2 displays...
Press...
3 ENTER
Clear the verification
counter
Clear Verification
lets you clear the verification counter for all the address-
able detectors in the system.
STATUS CHANGE Clear verify count 09:37A Wed 08/02/95
4 ENTER
Clear History
lets you clear the entire history buffer. To do so, follow these
steps.
Press...
and the CRT-2 displays...
Set Action/Alert
lets you set the prealarm for Alert or Action. For example,
Change Prealarm from Alert to Action. To do so, follow these steps.
Set the Prealarm for Alert
or Action
5 ENTER
Set Pre-alarm Alert(T)/Action(N). Type T or N then Enter
STATUS CHANGE Change Alert/Action 09:37A Wed 08/02/95
Pre-alarm now set for ACTION
Clear the entire history
buffer
Press...
and the CRT-2 displays...
N ENTER
************** History Clear ***************