2-62
AFP-400 Installation
PN
50253
:
A2 03/12/96
SLC Wiring with CMX Control Modules
Refer to Device Compatibil-
ity Document 15378 for
compatible notification
appliances.
When an MPS-400 Notification Appliance Circuit supplies power to CMX
modules:
1) The CMX module outputs are coded if the MPS-400 Notification Appli-
ance Circuit is coded.
2) Program the MPS-400 Notification Appliance Circuit for general alarm.
The wiring diagram below shows an NFPA Style Z Notification Appliance
Circuit (all circuits are supervised and power-limited) using a CMX module.
The following table contains SLC wiring connections to the MPS-400 and
CPU-400 as shown in the wiring diagram.
Module
Connect...
MPS-400
24V (+) to TB* terminal 1
24V () to TB* terminal 2
* NAC TB7, TB8, TB9, or TB10
CPU-400
SLC (+) to TB5-1
SLC () to TB5-3
Style Z NAC Circuits
to next device on
loop
+
CMX
CMX
NFPA Style Z Notification Appliance Circuit
CPU-400
MPS-400
MPS-400 and CPU-400 SLC Connections
Typical Style Z Wiring
Diagram