1-10
AFP-400 Installation
PN 50253:A2 03/12/96
End of Line Devices
System Components
The following table contains a list of the end-of-line devices that you can
install in an AFP-400 system.
Option
Description
Notes
System Sensor
(SSD) A2143-00
A 47K End-Of-Line Resistor
(ELR) Assembly ELR used in the
supervision of MMX-1 or
MMX-101 Monitor and CMX
Control Module circuits.
Supplied with MMX or CMX
modules.
System Sensor
(SSD) A2143-10
The 3.9K End-Of-Line Resistor
(ELR) Assembly used with the
MMX-2.
Supplied with MMX-2
modules.
N-ELR Resistor
Assortment
(N-ELR)
An N-ELR, required for
Canadian installations, provides
a variety of resistor values to
mount to a single ELR plate.
Resistors can be used for the
supervision of an MMX Monitor
Module or CMX Control Module
circuit.
Resistors included:
120 ohms
470 ohms
1.8K
2.2K
4.7K
6.8K
10K
27K
47K
Use 2.2K for the MPS-400
output;
Use 4.7K for ICM-4,
ICE-4, VCM-4, VCE-4, and
DCM-4; use 47K for
CMX, MMX-1, and
MMX-101 modules.