5-16
AFP-400 Installation
PN 50253:A2 03/12/96
Releasing Applications
This control panel can be used as a control panel for agent release or
preaction/deluge control applications. When used with compatible, listed
actuating and initiating devices, the system meets the requirements of the
following standards:
Standards
The AFP-400 supports a maximum of ten releasing circuits. You can divide
the releasing circuits between the MPS-400 releasing outputs, the ICM-4,
ICE-4, and CMX modules. For more information, refer to the AFP-400
Programming manual.
This section contains diagrams that show how to connect the following:
Connect a Releasing Device to the MPS-400.
Connect a Releasing Device to an ICM-4/ICE-4 Module.
Connect a Releasing Device to a CMX Module.
Connect an N-ARA-10 Agent Release-Abort Station.
Continued on the next page...
Connecting Releasing
Devices
Programming
NFPA Standards
Standard
Covers
NFPA 12
CO2 Extinguishing Systems (high pressure only)
NFPA 12A
Halon 1301 Extinguishing Systems
NFPA 12B
Halon 1211 Extinguishing Systems
NFPA 13
Sprinkler Systems
NFPA 15
Water Spray Systems
NFPA 16
Foam-water Deluge and Foam-water Spray Systems
NFPA 17
Dry Chemical Extinguishing Systems
NFPA 17A
Wet Chemical Extinguishing Systems
NFPA 2001
Clean Agent Fire Extinguishing Systems