AFP-400 Installation
PN 50253:A2 03/12/96
5-9
Combination Fire/Burglary Applications
You can use the control panel as a combination Fire/Burglary and Burglary
system when operated according to the instructions in this section.
For security applications, program one or more monitor modules with the
BURGLAR ALA type code, and wire as described in this section. Activating
this type of monitor module lights the Security LED, and displays a burglar
alarm condition on the control panel LCD. The piezo will sound until you
press <Acknowledge>. You can also program additional sounders or output
devices to activate with the burglar alarm initiating device. The BURGLAR ALA
type circuit is designed to indicate an alarm as follows: (a) on an open or
short circuit; or (b) on a ±50% change in resistance value from the EOL
resistor value.
A tamper switch installed in the cabinet also indicates a security alarm when-
ever the door is open. If the panel indicates a BURGLAR ALA or DOOR
TAMPER condition, you can acknowledge, silence, or reset the condition from
the panel.
When the system resets, a 30-second exit timer starts. During this time the
tamper switch and all BURGLAR ALA type alarms are ignored. There is no
entrance delay timer.
For bypass of security zones, use the DISABLE routine (covered in the STA-
TUS CHANGE section of the AFP-400 Operations Manual) for BURGLAR ALA
type devices.
Overview
Installing a Security
Tamper Switch into
the CAB-400AA
S2
J6
Installing the STS-200 Tamper Switch
1) Install the STS-200 tamper switch onto the CAB-400AA as shown below.
2) Connect the STS-200 connector to J5 (Tamper) on the MPS-400.
Wire the cabinet with a security tamper switch kit (see illustration below).
CAB-400AA cabinets require Tamper Switch model STS-200; CAB-3 cabinets
require model STS-1.
Installing a Security
Tamper Switch
MPS-400
STS-200 Tamper
Switch
MPS-400 J5
Tamper
General Operation