AFP-400 Installation
PN 50253:A2 03/12/96
E-7
Using the CRT-2 for Alter Status
1 1
1 1 1
ENTER
Overview
This section shows how to do Alter Status functions from a CRT-2.
Access the Alter Status function from the CRT-2 by following these steps.
1) Turn on the CRT-2 connected to the control panel.
2) Press the Alter Status function key. The control panel displays the Alter
Status menu options:
Accessing Alter Status
Options
Enter Status Change Password or Escape to Abort
3) Enter the Status Change Password. The factory default Status Change
Password is 11111. The password does not display on the CRT. Five
asterisks will appear in place of the password.
ALTER
STATUS
*****
1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clr History 5=Set Alert/
Action
Press...
Alter Status Options
From the Alter Status Options menu, you can select options 1-5.
The Alter Status Options menu appears.
Continued on the next page...
Table E-5 Alter Status Functions
Function
Lets you...
Disable
Enable or disable detectors, modules, or panel
circuits.
Alarm/Pre-alarm
Change the alarm and pre-alarm levels of any
addressable detector in the system.
Clear Verification Clear the verification counter for all the
addressable detectors in the system.
Clear History
Clear the contents of the history buffer.
Set Action/Alert
Set the pre-alarm for the Alert or Action.