2-2
AFP-400 Installation
PN
50253
:
A2 03/12/96
The following procedures, diagrams, and instructions must be followed
precisely to avoid damage to the control panel and other system components.
System reliability depends upon proper installation and maintenance.
Installation Tasks
o
Cabinet Door
Mount the cabinet door hardware (pre-mounted on a
CAB-400AA). Refer to Installing the Cabinet Door.
o
Chassis
Mount all chassis as shown in the installation drawing.
o
Main Power Supply
Mount the Main Power Supply (MPS-400) to the
cabinet.
Do not wire anything at this time!
o
Audio Visual Power Supplies
If installing optional Audio Visual Power
Supplies (AVPS-24), mount the AVPS-24 modules to the chassis. Refer to
the mounting diagrams.
o
Audio Visual Power Supply Cables
Connect the Trouble Cable(s) and
Auxiliary Bell Power Harness to the AVPS-24.
o
Auxiliary Relay Modules
Mount the ARM-4 modules into a chassis.
o
Preliminary System Wiring
Wire the Main Power Supply and any
AVPS-24s while the terminals are accessible. Refer to the MPS-400 and
AVPS-24 wiring diagrams.
o
Module Ribbon Cables
Connect the 1st Group Ribbon Cable of the
CPU-400. For each additional row of modules installed in the cabinet,
connect an Expander Row Ribbon Cable to the CPU-400.
o
CPU-400
Install the CPU-400 module in the top left cabinet position.
Connect the Power Ribbon and Power Harness between the CPU-400 and
the MPS-400/MPS-400PCA.
o
Module Expander Boards
If the system requires expander boards for a
module, install as illustrated.
o
Modules
Mount each module in its respective chassis position as illus-
trated in the drawings. Connect the CPU Row Ribbon Cable and the
Expander Row Ribbon to the modules. Field-wire each module, according
to its respective wiring diagram.
Continued on the next page...