AFP-400 Installation
PN 50253:A2 03/12/96
5-15
Block Diagram
20-Zone Code Connection Table
This section contains information for wiring modules for 20 coded Notification
Appliance Circuits (NACs). The connection table contains a list of connections
between the modules and the UZC-256. (All cables are PN 71091, except the
cable between the MPS-400 and the UZC-256.) Refer to the block diagram for
typical connections. Make sure to mate all connectors (except MPS-400, J3) as
shown in the figure to the left of the block diagram.
Module
Connector Connects to...
AVPS-24 #1 P3
UZC-256 P11
AVPS-24 #1 P3
UZC-256 P9
ICM-4
J5
J6
UZC-256 P10
ICE-4 J5
ICM-4
J5
J6
UZC-256 P8
ICE-4 J5
MPS-400
J3
UZC-256 TB1-8 (black wire)
(UZC-256 TB1-7
Zone Coding, continued
Wiring 20 Coded
Notification Appliance
Circuits (NACs)
MPS-400
TB-1
P9
P11
P10
P8
UZC-256
AVPS-24
#1
AVPS-24
#2
P3
J3
P3
3A Max.
3A Max.
3A Max.
3A Max.
Cable P/N
71093
J5
J5
J6
ICM-4
J6
ICE-4
J5
J5
J6
ICM-4
J6
ICE-4
These eight Notification
Appliance Circuits share
3 amps and are
powered from AVPS-24
#1.
These four coded Notification
Appliance Circuits are powered from
the MPS-400. The combined alarm
load on the MPS-400 cannot exceed 6
amps. Each NAC is rated at 2.5 amps
maximum.
These eight Notifica-
tion Appliance
Circuits share
3 amps and are
powered from AVPS-
24 #2.
Vertical
Connection
Horizontal
Connection
Typical Wiring for 20 Zone Codes