AFP-400 Installation
PN
50253
:
A2 03/12/96
2-41
Remote Printers and CRTs
You can also use the EIA-232
printer interface with EDP-
listed equipment, such as
personal computers, to
monitor the control panel for
supplementary purposes.
Remote Printers
Setting PRN-4 Options
The PRN-4 remote printer prints a copy of all status changes within the
AFP-400 and time-stamps the printout with current time of day and date.
The PRN-4 provides 80 columns of data on standard 9" by 11" tractor-feed
paper. This section contains information for setting the printer options and
connecting a printer to the AFP-400 control panel.
Refer to the documentation supplied with the PRN-4 for instructions on
using the printer menu controls. Set the printer options (under the menu
area) as listed in the following table.
DIP
Switches
System
Status
NAC 1
(B01)
Function
6
7
8
X
X
X
No Alarm
OFF
Standby
OFF
OFF
OFF
OFF
OFF
OFF
No Alarm
Alarm
ON
X
1000 Hz 1/2 sec on, 1/2 sec
off
Slow whoop
OFF
OFF
OFF
OFF
ON
ON
No Alarm
Alarm
ON
X
Horn
120ppm
OFF
OFF
ON
ON
OFF
OFF
No Alarm
Alarm
ON
X
Horn
Yelp
OFF
OFF
ON
ON
ON
ON
No Alarm
Alarm
ON
X
Yelp
Wail
ON
ON
OFF
OFF
OFF
OFF
No Alarm
Alarm
ON
X
3 slow whoops, VRAM-B
3 slow whoops, VRAM-A
ON
ON
OFF
OFF
ON
ON
No Alarm
Alarm
ON
X
VROM B
VROM A
ON
ON
ON
ON
OFF
OFF
No Alarm
Alarm
ON
X
20 ppm
VROM A & B
ON
ON
ON
ON
ON
ON
No Alarm
Alarm
ON
X
Horn
NFPA Uniform Code 3
temporal pattern fast whoop
X = Indicates that Switch or Control Point may be either "ON" or "OFF"
PRN-4 Setup Options
Continued on the next page...