2-36
AFP-400 Installation
PN
50253
:
A2 03/12/96
Category
Calculation Column 1
Primary, Non-Fire Alarm
Current (amps)
Calculation Column 2
Primary, Fire Alarm Current
(amps)
Calculation Column 3
Secondary, Non-Fire Alarm
Current (amps)
Qty
X [current
draw]=
total
Qty
X [current draw]=
total
Qty
X [current draw]=
total
Basic system
(CPU-400 + MPS-400)
1
x [ ] =
x [ ] =
0.225
1
x [ ] =
x [ ] =
0.420
1
x [ ] =
x [ ] =
0.170
AVPS-24
[ ]
x [0.009]=
[ ]
x [0.009]=
[ ]
x [0.009]=
ICM-4, CRM-4
ICE-4
CRE-4
DCM-4
VCE-4
VCM-4
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.007]=
x [0.001]=
not applicable
x [0.008]=
x [0.001]=
x [0.007]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.072]=
x [0.065]=
x [0.065]=
x [0.080]=
x [0.040]=
x [0.040]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.007]=
x [0.001]=
not applicable
x [0.008]=
x [0.001]=
x [0.007]=
AFM-16AT, AFM-32A
ACM-16AT, ACM-32A
AEM-16AT, AEM-32A
AFM-16A
LCD-80, LCD-80TM
ACM-8R (refer to Doc. 15342)
LDM (refer to Doc. 15885)
UZC-256
NIB-96
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
x [0.025]=
x [0.100]=
x [ ]=
x [ ]=
x [0.035]=
x [0.022]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.056]=
x [0.056]=
x [0.018]=
x [0.065]=
x [0.100]=
x [ ]=
x [ ]=
x [0.085]=
x [0.
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
x [0.025]=
x [0.050]=
x [ ]=
x [ ]=
x [0.035]=
x [0.022]=
AMG-1, AMG-E, ATG-2
FFT-7, FFT-7S
[ ]
[ ]
x [0.060]=
x [0.060]=
[ ]
[ ]
x [0.060]=
x [0.120]=
[ ]
[ ]
x [0.060]=
x [0.060]=
AA-30
AA-120
NOT APPLICABLE
[ ]
[ ]
x [0.045]=
x [0.050]=
2-Wire Smoke Detectors (refer to
the Device Compatibility
Document for current draws)
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
RPT-W, RPT-WF, RPT-F
RPT-485W
RPT-485WF
[ ]
[ ]
[ ]
x [0.017]=
x [0.017]=
x [0.017]=
[ ]
[ ]
[ ]
x [0.017]=
x [0.017]=
x [0.017]=
[ ]
[ ]
[ ]
x [0.017]=
x [0.017]=
x [0.017]=
SDX, CPX & FDX-551, SDX-551TH
MMX-1, MMX-101, CMX-1 BGX-101L
CMX-2
MMX-2 (see Doc. M500-03-00)
B601BH
B501BH (Horn in base)
DHX-501, DHX-502 (see instructions)
ISO-X
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
X [0.00020]=
X [0.00030]=
X [0.00030]=
X [ ]=
X [0.00100]=
X [0.00100]=
X [ ]=
X [0.00045]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
X [0.00020]=
X [0.00030]=
X [0.00030]=
X [ ]=
X [0.00100]=
X [0.00100]=
X [ ]=
X [0.00045]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
X [0.00020]=
X [0.00030]=
X [0.00030]=
X [ ]=
X [0.00100]=
X [0.00100]=
X [ ]=
X [0.00045]=
UDACT Communicator
[ ]
x [0.040]=
[ ]
x [0.100]=
[ ]
x [0.040]=
Notification Appliance powered
from MPS-400
(see note 1)
Not Applicable
[ ]
[ ]
x [ ]=
x [ ]=
Not Applicable
4-Wire Smoke Detectors
(see note 2)
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
Power Supervision Relays
(see note 2)
[ ]
x [ ]=
[ ]
x [ ]=
[ ]
x [ ]=
Other devices drawing power
from MPS-400 TB2
excluding smoke detectors
(see note 3)
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
Remote Station Circuits
[ ]
x [0.018]=
[ ]
x [0.018]=
[ ]
x [0.018]=
Sum each column for totals
Primary, non-alarm
total:
Primary, alarm total:
Secondary, alarm total:
Table 2-2 AFP-400 System Current Draw Calculations
1) For the MPS-400, enter the total notification appliance draw from the MPS-400, excluding
the current from AVPS-24 supplies.
2) The total regulated load current supplied to four-wire smoke detector and power supervi-
sion relays cannot exceed 1.25 amps.
3) TB-2 contains three power outputs. The load on a power output cannot exceed 1.25 amps.
4) The total regulator load cannot exceed 6 amps in alarm and 3 amps in standby.
How to Use
Table 2-2,
continued
Calculating the System Current Draw