AFP-400 Installation
PN 50253:A2 03/12/96
1-9
System Components
Addressable Modules:
CMX and MMX Modules
Addressable Modules
CMX Series Control Modules and MMX Series Monitor Modules provide an
interface between the control panel and conventional initiating and notifica-
tion devices. You can set all CMX and MMX modules to respond to an
address with built-in rotary decimal switches. A flashing LED indicates
communication between the module and the control panel. A CMX comes
with a thermoplastic cover for mounting to a 4-inch square mounting box.
MMX Module
CMX Module
BGX-101L Pull Station
Option
Description
Monitor Modules
MMX-1
MMX-2
Addressable Monitor Modules for monitoring
conventional initiating devices. The MMX-1 is used for
normally open contact alarm initiating devices, such as
manual pull stations, four-wire smoke detectors, heat
detectors, waterflow, security contacts, and supervisory
devices. Use the MMX-2 for specific two-wire smoke
detectors in addition to normally open contacts. Wire
supervised circuits as NFPA Style B or Style D circuits.
MMX-101
An Addressable Module that is functionally similar to an
MMX-1 Monitor Module (Style B circuits only), but
offered in a smaller package for mounting directly in the
electrical box of the device being monitored. It does not
include a blinking LED or a magnetic test switch.
Control Modules
CMX-1
CMX-2
Addressable Control Modules used as Notification
Circuits to power and supervise compatible, UL listed
notification appliances. Wire supervised circuits as
NFPA Style Y or Style Z. Breaking the two built-in tabs
allows using the CMX as a Form-C control relay. The
CMX-2 is rated for higher voltage applications (70.7 V).
Loop Isolator Module
(ISO-X)
The ISO-X is an automatic switch that opens the circuit
voltage to a communications loop branch(es) whenever
a fault is detected on that circuit. The remainder of the
communications loop leading up to the ISO-X continues
to operate, unaffected by the fault.
BGX-101L
A dual action addressable manual pull station featuring
a key-lock reset. The pull station includes an MMX-101
and responds to an address set with built-in rotary
decimal switches.