AFP-400 Installation
PN 50253:A2 03/12/96
5-3
NFPA 72-1993 Remote Station Fire Alarm System
The diagram shows typical wiring for NFPA 72-1993 Remote Station Fire Alarm
System (FireLite RS82 Remote Station Receiver). Note the following:
1) This application is intended for connection to a polarity reversal circuit of a
remote station receiving unit having compatible ratings.
2) All connections are power limited and supervised with the exception of the
reverse polarity loop.
3) Loop supervision is the responsibility of the receiver.
4) Remote Alarm and Remote Trouble wiring can leave the building.
5) Maximum load for each circuit: 10 mA; Reverse polarity output voltage:
24 VDC (nominal) or 28 VDC (max).
FireLite RS82 Remote
Station Receiver UL
listed. Refer to
FireLite Alarms, Inc.,
Instruction Manual for
Remote Station
Receiver Model RS-82.
4XTM
Transmitter Module
(activated polarities shown)
+ +
1
2
3
4
Remote Alarm
Remote Trouble
Wiring Diagram
Overview
Remote Station Connection Using 4XTM Module