AFP-400 Installation
PN 50253:A2 03/12/96
5-11
Combination Fire/Burglary Applications, continued
The following diagram shows a typical wiring diagram for proprietary burglar
alarm applications with a CMX configured as an Notification Appliance Circuit.
Note the following:
1) The CMX is configured as an Notification Appliance Circuit (do not break
tabs) and programmed in the Protected Premises Unit.
2) Supplementary use only in UL Listed Systems.
Refer to Device Compatibility Document 15378 for compatible Notification
Appliance Circuits.
Wiring
+
-
+
SLC Loop
Channel A or B
()
(+)
UL-listed 24 VDC
Power Supply
47K
End-of-
Line
Resistor
To next
device
47K
End-of-
Line
Resistor
47K
End-of-
Line
Resistor
MMX-1
CMX
MMX-1
MMX-1s are pro-
grammed with software
type BURGLAR ALA.
Wiring Diagram
UL-listed, normally-open
security switch
UL-listed, normally-closed
security switch
UL-listed, normally-closed
security switch
UL-listed, normally-
closed security switch
AFP-400 Protected Premises Unit
+24 VDC UL-listed
Notification Appliance
Wiring Diagram for Proprietary Burglar Alarm Applications