F-1
Appendix F: UL Power Limited Wiring Requirements
Overview
Power limited and nonpower limited circuit wiring must remain separated
in the cabinet. All power limited circuit wiring must remain at least
0.25 inches from any nonpower limited circuit wiring. All power limited
and nonpower limited circuit wiring must enter and exit the cabinet through
different knockout and or conduits.
Power Limited Modules
and Circuits
The following table lists all power limited modules and circuits compatible
with the AFP-400.
All nonpower limited circuits
connected to ACM-8R, ARM-4,
CRM-4, CRE-4, and LDM-R32
modules must be identified in
the space provided on the
cabinet door label.
Power Limited Components
Power Limited Components
Include the following...
Modules with power limited
circuits
ACM-16A
AEM-16A
ACM-32A
ARM-32A
AFM-16A
AFM-16A
AFM-32A
ACT-1
AMG-1
AMG-E
AMG-2
CPU-400
DCM-4
FFT-7
FFT-7S
ICM-4
ICE-4
LCD-80
LCD-80TM
LDM-32
LDM-32E
NIB-96
RPT-485
UDACT
UZC-256
VCE-4
VCM-4
Modules with nonpower circuits AA-30
AA-100
AA-120
AVPS-24
MPS-400
4XTM
AC and battery circuits
are nonpower limited
Municipal Box circuit is
nonpower limited
Circuits (dry contacts) on theses
modules when connected to
power limited sources
ACM-8R
ARM-4
CRM-4
CRE-4
LDM-R32